Eaton FD140 DPCT Fire diesel fire pump controller

The Eaton FD140 DPCT Fire diesel fire pump controller.

Eaton FD140 DPCT Fire diesel fire pump controller is Eaton’s touchscreen controller for diesel fire pump engines. It follows the same design as Eaton’s EPCT series controllers and is built to the latest edition of NFPA 20, with UL and FM approval and an optional CE mark.

7-inch color touchscreen

The controller is run from a 7-inch, 800 by 480 color touchscreen, rated Type 4X. Nine tabs cover the whole job: Home, Startup, Panel Setup, Help, Pressure Settings, Timer Values, Alarm Setpoints, Inputs/Outputs, and History, Statistics and Diagnostics.

Startup covers quick setup, manual and automatic starts, and alarm tests. Panel Setup covers language, date and time, and nominal voltage. Pressure Settings cover start and stop pressure, low and high pressure alarms, low suction shutdown, and transducer calibration.

Timer Values cover minimum run time, sequential start, AC power failure start, and the weekly engine test. Alarm Setpoints cover source and battery voltage, transducer-fail engine start, and aborting an engine test. The History tab keeps up to 65,000 alarms and messages, with statistics on engine run time, starts, voltages, and system pressure.

Inputs, outputs and battery chargers

The I/O board takes 10 custom inputs, programmable for 20 preset conditions, and output relays programmable for 61 conditions, with up to 4 optional boards: a relay board, MODBUS, and a secondary 4-20 mA output. The board accepts a 12 to 24 VDC battery and 120 to 240 VAC utility power.

Three relays are rated 250 VAC, 9 A, and one is rated 250 VAC, 10 A, covering Common Alarm, Low Fuel, Auto Mode, and Engine Run, each with a surface-mount LED. Twin battery chargers run on 120 to 240 VAC, 50/60 Hz, auto-switching, with 12 or 24 VDC selectable by dipswitch, for lead-acid or nickel-cadmium batteries.

Charging is three-step: bulk up to 10 A to about 90 percent, overcharge at 1.5 A to 99 percent, then float. A drain valve solenoid runs manual and automatic engine tests. An external USB port takes history, statistics, diagnostics, the startup file, and the configuration.

Specifications

Operating temperature 4 to +50 °C (39 to +122 °F) for the Eaton FD140 DPCT Fire diesel fire pump controller. The standard enclosure is UL Type 2 drip-proof, with Types 3, 3R, 4, 4X, and 12 available, and the controller meets U.B.C./C.B.C. seismic requirements.

The pressure sensor is solid-state 4 to 20 mA, with start and stop adjustable in 1 PSI steps. The controller is available in 8 languages: English, French, Spanish, Portuguese, Turkish, Italian, Dutch, and Polish. Approvals: UL and UL Canada (UL218), Factory Mutual, CE mark optional.

Dimensional drawing

Eaton FD140 DPCT Fire dimensional drawing CE16780H01

Download dimensional drawing (PDF)

Drawing CE16780H01, Revision 001, dated 08/30/22, covers enclosure Types 2, 3, 3R, 4, 4X, and 12. Dimensions in inches [mm]: 27.31 [694], 11.23 [285], 9.08 [231], 24.30 [617], 21.00 [533], 29.02 [737], 27.52 [699], 13.00 [330], 9.67 [246]. Piping entrance is 1/2-inch NPT female, top and bottom. All enclosures are finished in red.

Legend:

  1. DPCT Touchscreen
  2. External USB Port
  3. Manual-Off-Auto Switch
  4. Crank #1 Pushbutton
  5. Crank #2 Pushbutton
  6. Stop Pushbutton
  7. Flange Mounted Buzzer
  8. Cable Access
  9. Lockable quarter-turn

Wiring schematic and field connections

Eaton FD140 DPCT Fire wiring schematic CE16781H01

Eaton FD140 DPCT Fire field connections CE16782H01

Wiring schematic CE16781H01 and field connections CE16782H01, both Revision 001, 08/30/22. Common alarm relays are energized under normal conditions; all relay contacts are shown in the no-power condition.

Alarm contacts are rated 8 A / 240 VAC and engine run contacts 10 A / 240 VAC; alarm and engine wiring is copper conductors only. Customer inputs 1 to 10; alarm contacts Engine Run 50–55, Low Fuel 56–61, Auto Mode 62–67, Common Alarm 68–73; optional output boards 1CR–4CR. Wire sizes: I/O board inputs and outputs stranded #14; engine connections stranded #14; battery connections stranded #10 for 0–25 ft and stranded #8 for 25–50 ft.

These drawings cover the field wiring of the Eaton FD140 DPCT Fire diesel fire pump controller.

Options

The Eaton FD140 DPCT Fire diesel fire pump controller is ordered as model FDF14 with options for language (English, French, Italian, Spanish, Portuguese, Chinese, Polish, Dutch, Turkish), supply voltage (380/400/415/480/600), enclosure (NEMA 3R, 4, 12, 3, 4X stainless or painted steel), tropicalization, engine heater circuit, export crating, powered louver contacts, nickel-cadmium batteries, relay card, MODBUS, secondary 4-20 mA, pressure switches, space heaters, fuel level switches, and a terminal block enclosure.

All controllers are factory set for 12 Vdc unless otherwise noted.

Downloads

Download documentation for the Eaton FD140 DPCT Fire diesel fire pump controller:

More on the Eaton FD140 DPCT Fire diesel fire pump controller: Eaton fire pump controllers | Diesel – FD140 Components | Eaton Fire Pump Control Spares